Quick Overview
Silent Knight 5495 power supply module The SIL-5495 is a 6 amp power supply module that provides its own AC power and charging circuit for batteries. It also has its...

Available : In Stock

$346.95

Ship out same day or within 24 hours
Add to Wishlist

Silent Knight 5495 power supply module

The SIL-5495 is a 6 amp power supply module that provides its own AC power and charging circuit for batteries. It also has its own back up battery.

The 5495 can provide supervision functions as well in the following cases:

  • Low AC power
  • Low battery condition
  • Earth ground fault
  • Auxiliary output power limit condition
  • EOL supervision trouble or power limited condition at an output


Whenever a trouble condition occurs this unit will then, in turn, create a trouble condition on the main panel that it is connected to. The 5495 also contains a Form C relay output for trouble conditions as an alternative to the notification of circuit trouble that the unit already has.

Specifications:

Electrical Specification
AC input: 120 VAC at 2 amps
Output: 24 VDC at 6 amps
Current:
Standby 75 mA
Alarm 205 mA
Auxiliary power circuit: 1
Notification circuits: 4
Output configuration: 2 Class A (Style Z) 4 Class B (Style Y) (1 Class A & 2 Class B) Amps per output circuit: 3.0 (6.0 amps total)
Notification circuit output: 20.4 to 27.3 VDC @ 3.0 amps each, 4.7 kW EOL resistor required on each Class B circuit
No. of inputs 2
Input configuration: 2 Class B or 2 Class A Input
voltage range: 9 - 32 VDC
Battery charging capacity: 35.0 AH
Ambient temp.: 32 to 120 F (0 to 49 C)

Mechanical
Dimensions: 12.25" W x 16" H x 3" D (30.88 cm W x 40.64 cm H x 7.62 D cm)

Indicator Lights
AC power on : Green
Battery trouble: Yellow
Ground fault: Yellow
Aux trouble: Yellow
Output troubles (1-4): Yellow

Features

  • UL Listed for 6 amps of notification power
  • Power supply's advanced switch mode design reduces damaging heat and manages power up to 50% more efficiently than other systems
  • Dip switches allow for easy reconfiguration
  • 24 VDC filtered output voltage
  • Four power-limited notification outputs; 2 Class A or 4 Class B, or 1 Class A and 2 Class B
  • Additional continuous auxiliary output
  • 3 amps per output circuit
  • 2 inputs; 2 Class B or 2 Class A
  • Ground fault detector/indicator
  • Independent trouble relay
  • AC loss delay option shuts off power to non-essential high-current accessories like magnetic door holders
  • Built-in synchronization for appliances from System Sensor, Gentex, AMSECO, Wheelock and Faraday
  • Stand alone operation
  • Lightweight design adds to ease of installation and reduces shipping costs
  • Operates with most polarized, UL Listed notification devices
  • ANSI Cadence pattern output capability built-in

Extended Information