Fire-Lite FCPS24FS8 8 amp Power Supply and Battery charger

Quick Overview
Fire-Lite FCPS24FS8 8 amp Power Supply and Battery charger The FCPS24FS8 is an 8 amp remote power supply with battery charger. May be used with 12 or 24volt systems. This...

Available : In Stock

$396.95

Ship out same day or within 24 hours
Add to Wishlist

Fire-Lite FCPS24FS8 8 amp Power Supply and Battery charger

The FCPS24FS8 is an 8 amp remote power supply with battery charger. May be used with 12 or 24volt systems. This unit will supply additional power for accessories such as bells or any other device that needs power. You can use it when you have maxed out the power outputs on your main panel.

This also features a battery charging circuit which can charge up to 18 A battery.

Specifications:

  • Primary (AC) Power:
    • FCPS-24FS8: 120 VAC, 60 Hz, 3.2A maximum.
    • FCPS-24FS8/E: 240 VAC, 50 Hz, 1.6A maximum.
    • Wire Size: minimum #14 AWG (2.0mm2) with 600 V insulation.
  • Control Input Circuit:
    • Trigger Input Voltage: 9 to 32 VDC.
    • Trigger Current: 2.0 mA (16 - 32 V); Per Input: 1.0 mA (9- 16 V).
  • Trouble Contact Rating: 5 A at 24 VDC.
  • Auxiliary Power Output: Specific application power 500 mA maximum.
  • Output Circuits:
    • +24 VDC filtered, regulated.
    • 3.0 A maximum for any one circuit.
    • Total continuous current for all outputs (stand-alone mode):
    • FCPS-24FS8: 6.0 A maximum.
    • Total short-term current for all outputs (NAC expander mode):
    • FCPS-24FS8: 8.0 A maximum.

Features

  • UL-Listed Notification Appliance Circuit (NAC) synchronization using System Sensor, Wheelock, or Gentex
  • Commander2 appliances.
  • Operates as a 'sync-follower' or as a 'sync-generator' (default). 
  • Contains two fully-isolated input/control circuits - triggered from FACP NAC (NAC expander mode) or jumped permanently
  • 'ON' (stand-alone mode).
  • Two Class B (Style Y) or Class A (Style Z, with ZNAC-4 module) NACs (circuits 1 & 3)
  • 8-amp full load output, with 3 amps maximum/circuit, in
  • NAC expander mode (UL 864).
  • 6-amp continuous output in stand-alone mode (UL 1481).
  • Compatible with coded inputs; signals passed through.
  • Optional power-supervision relay (EOLR-1).
  • In stand-alone mode, output power circuits may be configured as: resettable, (reset line from FACP required), non-resettable, or a mix of two and two.
  • Fully regulated and filtered power output - optimal for powering four-wire smoke detectors, annunciators, and other system peripherals requiring regulated/filtered power.
  • Power-limiting technology meets UL power-limiting requirements.
  • Form-C normally-closed trouble relay.
  • Fully supervised power supply, battery, and NACs.
  • Selectable earth fault detection.
  • AC trouble report selectable for immediate 2-hour delay.
  • Works with virtually any UL 864 fire alarm control which utilizes an industry-standard reverse-polarity notification circuit (including unfiltered and unregulated bell power).
  • Requires input trigger voltage of 9 - 32 VDC.
  • Self-contained in compact, locking cabinet - 15" H x 14.5" W x 2.75" D (cm: 38.1H x 36.83W x 6.985D).
  • Includes integral battery charger capable of charging up to 18 AH batteries. Cabinet capable of housing 7.0 AH batteries.
  • Battery charger may be disabled via DIP switch for applications requiring larger batteries.
  • Fixed, clamp-type terminal blocks accommodate up to 12
  • AWG (3.1mm2) wire.

Extended Information