Home > Fire Alarm Systems > Fire-Lite Commercial Fire Alarm Systems >

Fire-Lite FCPS24FS6 6amp Power Supply and Battery Charger
Fire-Lite FCPS24FS6 6amp Power Supply and Battery Charger

Our Price: $356.95

Availability: IN STOCK: Ships out same day or within 24 hours
Product Code: FIL-FCPS24FS6


Fire-Lite FCPS24FS6 6amp Power Supply and Battery Charger

The FCPS24FS6 is an 6 amp remote power supply with battery charger. May be used with 12 or 24volt systems. This unit will supply additional power for accessories such as bells or any other device that needs power. You can use it when you have maxed out the power outputs on your main panel.

This also features a battery charging circuit which can charge up to 18 A battery.


Primary (AC) Power
• FCPS-24FS6: 120 VAC 60 Hz, 3.2 A maximum
• Wire size: minimum 14 AWG (2.0 mm²) with 600V insulation.
Control Input Circuit
• Trigger Input Voltage: 9.0 to 32 VDC.
• Trigger Current: 2.0 mA (16 - 32 V).
(per input) 1.0 mA (9 - 16 V).
Trouble Contact Rating
• 5.0 A at 24 VDC.
Auxiliary Power Output
• Specific Application Power - 500 mA maximum.
Output Circuits
• +24 VDC filtered, regulated.
• 3.0 A maximum for any one circuit.
• 4.0 A maximum total continuous current for all outputs
(Stand-alone mode).
• 6.0 A maximum total short-term current for all outputs
(NAC Expander mode).
Secondary Power (Battery) Charging Circuit
• Supports lead-acid batteries only.
• Float Charge Voltage: 27.6VDC.
• Maximum Charge Current: 1.5 A.
• Maximum Battery Capacity: 18 AH.

  • UL Listed NAC Synchronization using System Sensor,
    Wheelock or Gentex (Commander Series) appliances.
    • Cascadable up to 10 power supplies (four with Gentex)
    with strobe timing maintained.
    • Operates as a sync follower or a sync generator (default).
    • Contains two, fully-isolated input/control circuits (triggered
    from FACP Notification Appliance Circuit [NAC
    expander mode] or jumpered permanently on [standalone
    • Optional mounting kit, P/N 90286, to internally house
    addressable SLC control module (CRF-300 or CMF-
    300) for alarm activation.
    • Four Class B (Style Y) or four Class A (Style Z) (with ZNAC-
    4 Module) Notification Appliance Circuits.
    • 6.0 A full load output (3.0 A maximum per circuit) in NAC
    expander mode (UL 864).
    • 4.0 A continuous output in stand-alone mode (UL 1481).
    • In stand-alone mode, output power circuits may be
    configured as resettable (reset line from FACP required)
    or non-resettable or a mix of two and two.
    • Fully regulated and filtered power output (optimal for
    powering four-wire smoke detectors, annunciators and
    other system peripherals requiring regulated/filtered
    • Power-limiting technology meets UL power-limiting requirements.
    • Form-C normally-closed trouble relay.
    • Fully supervised power supply, battery and Notification
    Appliance Circuits.
    • Selectable earth fault detection.
    24 Volt, 6 Amp Remote Power Supply
    DF-52301 • D-025
    Section: Power Supplies/Accessories
    July 8, 2004
    • AC trouble report selectable for immediate or 8 hour
    • Works with virtually any UL 864 fire alarm control which
    utilizes an industry-standard reverse-polarity notification
    circuit (including unfiltered and unregulated bell
    • Requires input trigger voltage of 9.0 - 32 VDC.
    • Self-contained in compact, lockable cabinet (15" [38.1
    cm] H x 14.5" [36.8 cm] W x 2.75" [7.0 cm] D).
    • Includes integral battery charger capable of charging up
    to 18 AH batteries. Cabinet capable of housing 7.0 AH
    • Battery charger may be disabled via dip switch for applications
    requiring larger batteries.
    • Fixed, clamp-type terminal blocks accommodate up to
    12 AWG (3.1 mm²) wire.

Share your knowledge of this product with other customers... Be the first to write a review

Browse for more products in the same category as this item:

Fire Alarm Systems > Fire-Lite Commercial Fire Alarm Systems